Zoom the image with the mouse

FC-102N110T4E54H4XGC3XXSXXXXAXB0CXXXXDX

Write a Review
SKU:
132L4251

Frequency ConverterFC-102N110T4E54H4XGC3XXSXXXXAXB0CXXXXDX VLT® HVAC Drive FC-102(N110) 110 KW / 150 HP, Three phase, 380 - 480 VAC,(E54) IP54 / Type …

Ask for a Quotation

Ask for a Quotation

Feel free to inquire
  • Security Image 1
Description

Frequency Converter
FC-102N110T4E54H4XGC3XXSXXXXAXB0CXXXXDX

VLT® HVAC Drive FC-102
(N110) 110 KW / 150 HP,
Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
RFI class A1 (C2)
No brake chopper
Graphical Loc. Cont. Panel
Coated PCB, Mains Disconnect + Fuse
Latest release std. SW.
Frame: D5H
No A Option, MCB-109 I/O, RTC Back-up
No C1 option, No D option

Other options according to Model Code

Model code: FC-102N110T4E54H4XGC3XXSXXXXAXB0CXXXXDX

Danfoss VLT® HVAC Drive FC-102 Drive is dedicated toventilation, heating, and refrigeration applications. With a wide rangeof powerful standard and optional features, the Drive provides th...

Gross weight 166.3 Kilogram
Net weight 166 Kilogram
EAN 5714853436965

 

Product View (Switch) GLBL Global (Standard)
Product Group FC- VLT® HVAC Drive FC-
Series 102 102
Power Rating N110 (N110) 110 KW / 150 HP
Phase T Three phase
Mains Voltage 4 380 - 480 VAC
Enclosure E54 (E54) IP54 / Type 12
RFI Filter H4 RFI class A1 (C2)
Brake - Safe Stop X No brake chopper
LCP G Graphical Loc. Cont. Panel
Coating PCB C Coated PCB
Mains Option 3 Mains Disconnect + Fuse
Adaptation A X Standard Cable Entries
Adaptation B X No adaptation
Software Release SXXX Latest release std. SW.
Software Language Pack X Standard Language Pack
A Option AX No A Option
B Option B0 MCB-109 I/O, RTC Back-up
C0 Option MCO CX No C0 option
C1 Option X No C1 option
C Option Software XX No software option
D Option DX No D option
Frame Size D5H D5H
Product Catalog NO_VIEW NO VIEW
Typecode Part 2 3XXSXXXXAXB0CXXXXDX
Power 110% (NO) [KW] 110 110
Height [mm] 1324,0 1324,0
Width w/ no C options [mm] 325,0 325,0
Depth [mm] 381,0 381,0
Depth with Option A/B [mm] 381,0 381,0
kVA 147 147
Power Loss NO [W] 2555 2555
Power Loss NO [W] 2257 2257
Continuous Current (NO) [A] 212 212
Intermittent Current (NO) [A] 233 233
Continuous Current (NO) [A] 190 190
Intermittent Current (NO) [A] 209 209
Calculated Gross Weight [kg] 166.3
Calculated Net Weight [kg] 166
ECCN EU Y901 Y901
ECCN US 3A999.a 3A999.a
Vendor ERR01 Cannot Determine Vendor
Recommended Factory ERR01 Cannot Determine Vendor
Modelcode01 FC-102N110T4E54H4XGC
Modelcode02 3XXSXXXXAXB0CXXXXDX
Recommended Plant ERR01 ERR01