Zoom the image with the mouse

FC-102N110T4E5MH2TLC3XQLX1XXAQBXCXXXXDX

Write a Review
SKU:
132H8365

Frequency ConverterFC-102N110T4E5MH2TLC3XQLX1XXAQBXCXXXXDX VLT® HVAC Drive FC-102(N110) 110 KW / 150 HP, Three phase, 380 - 480 VAC,IP54/Type 12+main …

Ask for a Quotation

Ask for a Quotation

Feel free to inquire
  • Security Image 1
Description

Frequency Converter
FC-102N110T4E5MH2TLC3XQLX1XXAQBXCXXXXDX

VLT® HVAC Drive FC-102
(N110) 110 KW / 150 HP,
Three phase, 380 - 480 VAC,IP54/Type 12+main shield
RFI Filter
Safe Stop
Graphical LCP + USB
Coated PCB, Mains Disconnect + Fuse
Condition Based Monitoring CBM
Frame: D5H
Modbus TCP MCA 122, No B Option
No C1 option, No D option

Other options according to Model Code

Model code: FC-102N110T4E5MH2TLC3XQLX1XXAQBXCXXXXDX

Danfoss VLT® HVAC Drive FC-102 Drive is dedicated toventilation, heating, and refrigeration applications. With a wide rangeof powerful standard and optional features, the Drive provides th...

Gross weight 128 Kilogram
Net weight 88 Kilogram
EAN 5714853375196

 

Product View (Switch) GLBL Global (Standard)
Product Group FC- VLT® HVAC Drive FC-
Series 102 102
Power Rating N110 (N110) 110 KW / 150 HP
Phase T Three phase
Mains Voltage 4 380 - 480 VAC
Enclosure E5M IP54/Type 12+main shield
RFI Filter H2 RFI Filter
Brake - Safe Stop T Safe Stop
LCP L Graphical LCP + USB
Coating PCB C Coated PCB
Mains Option 3 Mains Disconnect + Fuse
Adaptation A X Standard Cable Entries
Adaptation B Q Heat-sink access
Software Release LX1X Condition Based Monitoring CBM
Software Language Pack X Standard Language Pack
A Option AQ Modbus TCP MCA 122
B Option BX No B Option
C0 Option MCO CX No C0 option
C1 Option X No C1 option
C Option Software XX No software option
D Option DX No D option
Frame Size D5H D5H
Product Catalog NO_VIEW NO VIEW
Typecode Part 2 3XQLX1XXAQBXCXXXXDX
Power 110% (NO) [KW] 110 110
Height [mm] 1324,0 1324,0
Width w/ no C options [mm] 325,0 325,0
Depth [mm] 381,0 381,0
Depth with Option A/B [mm] 381,0 381,0
kVA 147 147
Power Loss NO [W] 2555 2555
Power Loss NO [W] 2257 2257
Continuous Current (NO) [A] 212 212
Intermittent Current (NO) [A] 233 233
Continuous Current (NO) [A] 190 190
Intermittent Current (NO) [A] 209 209
Calculated Gross Weight [kg] 166.3
Calculated Net Weight [kg] 166
ECCN EU Y901 Y901
ECCN US 3A999.a 3A999.a
Vendor ERR01 Cannot Determine Vendor
Recommended Factory ERR01 Cannot Determine Vendor
Modelcode01 FC-102N110T4E5MH2TLC
Modelcode02 3XQLX1XXAQBXCXXXXDX
Recommended Plant ERR01 ERR01
Bottom Banner