Zoom the image with the mouse

FC-102N400T4E5MH2TLC7XQLX1XXAXBXCXXXXDX

Write a Review
SKU:
132N5657

Frequency ConverterFC-102N400T4E5MH2TLC7XQLX1XXAXBXCXXXXDX VLT® HVAC Drive FC-102(N400) 400 KW / 550 HP, Three phase, 380 - 480 VAC,IP54/Type 12+main …

Ask for a Quotation

Ask for a Quotation

Feel free to inquire
  • Security Image 1
Description

Frequency Converter
FC-102N400T4E5MH2TLC7XQLX1XXAXBXCXXXXDX

VLT® HVAC Drive FC-102
(N400) 400 KW / 550 HP,
Three phase, 380 - 480 VAC,IP54/Type 12+main shield
RFI Filter
Safe Stop
Graphical LCP + USB
Coated PCB, Fuse
Condition Based Monitoring CBM
Frame: E1H
No A Option, No B Option
No C1 option, No D option

Other options according to Model Code

Model code: FC-102N400T4E5MH2TLC7XQLX1XXAXBXCXXXXDX

Danfoss VLT® HVAC Drive FC-102 Drive is dedicated toventilation, heating, and refrigeration applications. With a wide rangeof powerful standard and optional features, the Drive provides th...

Gross weight 295.3 Kilogram
Net weight 295 Kilogram
EAN 5715253096858

 

Product View (Switch) GLBL Global (Standard)
Product Group FC- VLT® HVAC Drive FC-
Series 102 102
Power Rating N400 (N400) 400 KW / 550 HP
Phase T Three phase
Mains Voltage 4 380 - 480 VAC
Enclosure E5M IP54/Type 12+main shield
RFI Filter H2 RFI Filter
Brake - Safe Stop T Safe Stop
LCP L Graphical LCP + USB
Coating PCB C Coated PCB
Mains Option 7 Fuse
Adaptation A X Standard Cable Entries
Adaptation B Q Heat-sink access
Software Release LX1X Condition Based Monitoring CBM
Software Language Pack X Standard Language Pack
A Option AX No A Option
B Option BX No B Option
C0 Option MCO CX No C0 option
C1 Option X No C1 option
C Option Software XX No software option
D Option DX No D option
Frame Size E1H E1H
Product Catalog NO_VIEW NO VIEW
Typecode Part 2 7XQLX1XXAXBXCXXXXDX
Power 110% (NO) [KW] 400 400
Height [mm] 2000,0 2000,0
Width w/ no C options [mm] 600,0 600,0
Depth [mm] 510,0 510,0
Depth with Option A/B [mm] 510,0 510,0
kVA 516 516
Power Loss NO [W] 8036 8036
Power Loss NO [W] 6933 6933
Continuous Current (NO) [A] 745 745
Intermittent Current (NO) [A] 820 820
Continuous Current (NO) [A] 678 678
Intermittent Current (NO) [A] 746 746
Calculated Gross Weight [kg] 295.3
Calculated Net Weight [kg] 295
ECCN EU Y901 Y901
ECCN US 3A999.a 3A999.a
Plant from Orderline F605 F605
Vendor ERR01 Cannot Determine Vendor
Recommended Factory ERR01 Cannot Determine Vendor
Modelcode01 FC-102N400T4E5MH2TLC
Modelcode02 7XQLX1XXAXBXCXXXXDX
Bottom Banner