Frequency converter
FC-302N110T5E20H2BGCXXXSXXXXALB2CXXXXD0
VLT® AutomationDrive FC-302
(N110) 110 KW / 150 HP,
Three phase, 380 - 500 VAC,(E20) IP20 / Chassis
RFI Filter
Brake chopper
Graphical Loc. Cont. Panel
Coated PCB, No Mains Option
Latest release std. SW.
Frame: D3H
PROFINET MCA 120, MCB-112 PTC Therm. Card
No C1 option, MCB-107 24V DC backup
ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Other options according to Model code
The VLT® AutomationDrive represents a single drive concept that controlsthe entire range of operations from ordinary to servo like applicationson any machine or production line.
| Gross weight | 62.3 Kilogram | ||
| Net weight | 62 Kilogram | ||
| EAN | 5710107953448 |
| Product View (Switch) | GLBL | Global (Standard) | |
| Product Group | FC- | VLT® AutomationDrive FC- | |
| Series | 302 | 302 | |
| Power Rating | N110 | (N110) 110 KW / 150 HP | |
| Phase | T | Three phase | |
| Mains Voltage | 5 | 380 - 500 VAC | |
| Enclosure | E20 | (E20) IP20 / Chassis | |
| RFI Filter | H2 | RFI Filter | |
| Brake - Safe Stop | B | Brake chopper | |
| LCP | G | Graphical Loc. Cont. Panel | |
| Coating PCB | C | Coated PCB | |
| Mains Option | X | No Mains Option | |
| Adaptation A | X | Standard Cable Entries | |
| Adaptation B | X | No adaptation | |
| Software Release | SXXX | Latest release std. SW. | |
| Software Language Pack | X | Standard Language Pack | |
| A Option | AL | PROFINET MCA 120 | |
| B Option | B2 | MCB-112 PTC Therm. Card | |
| C0 Option MCO | CX | No C0 option | |
| C1 Option | X | No C1 option | |
| C Option Software | XX | No software option | |
| D Option | D0 | MCB-107 24V DC backup | |
| Frame Size | D3H | D3H | |
| Typecode Part 2 | XXXSXXXXALB2CXXXXD0 | ||
| Product Catalog | NO_VIEW | NO VIEW | |
| Power 150% (HO) [KW] | 110 | 110 | |
| Power 110% (NO) [KW] | 132 | 132 | |
| Height [mm] | 909,0 | 909,0 | |
| Height w/ Regen/Loadshare [mm] | 1004,0 | 1004,0 | |
| Width w/ no C options [mm] | 250,0 | 250,0 | |
| Depth [mm] | 375,0 | 375,0 | |
| Depth with Option A/B [mm] | 375,0 | 375,0 | |
| kVA | 147 | 147 | |
| Power Loss NO [W] | 2954 | 2954 | |
| Power Loss NO [W] | 2724 | 2724 | |
| Power Loss HO [W] | 2289 | 2289 | |
| Power Loss HO [W] | 2051 | 2051 | |
| Continuous Current (NO) [A] | 260 | 260 | |
| Intermittent Current (NO) [A] | 286 | 286 | |
| Continuous Current (NO) [A] | 240 | 240 | |
| Intermittent Current (NO) [A] | 264 | 264 | |
| Continuous Current (HO) [A] | 212 | 212 | |
| Intermittent Current (HO) [A] | 318 | 318 | |
| Continuous Current (HO) [A] | 190 | 190 | |
| Intermittent Current (HO) [A] | 285 | 285 | |
| ATEX Marking 1 | ATEX: II (2) G [Ex eb Gb] [Ex | ATEX: II (2) G [Ex eb Gb] [Ex | |
| ATEX Marking 2 | db Gb] / II (2) D [Ex tb Db] | db Gb] / II (2) D [Ex tb Db] | |
| Calculated Gross Weight [kg] | 62.3 | ||
| Calculated Net Weight [kg] | 62 | ||
| ECCN EU | Y901 | Y901 | |
| ECCN US | 3A999.a | 3A999.a | |
| Vendor | ERR01 | Cannot Determine Vendor | |
| Recommended Factory | ERR01 | Cannot Determine Vendor | |
| Modelcode01 | FC-302N110T5E20H2BGC | ||
| Modelcode02 | XXXSXXXXALB2CXXXXD0 | ||
| Recommended Plant | ERR01 | ERR01 |