Frequency converter
FC-302N710T7E20H2XGCXXXSXXXXAXBKCXXXXD0
VLT® AutomationDrive FC-302
(N710) 710 KW / 1000 HP, Specific Ratings: 560kW@525-550V, 750HP@575V, 710kW@690V
Three phase, 525 - 690 VAC *,(E20) IP20 / Chassis
RFI Filter
No brake chopper
Graphical Loc. Cont. Panel
Coated PCB, No Mains Option
Latest release std. SW.
Frame: E4H
No A Option, MCB-101 General purp. I/O
No C1 option, MCB-107 24V DC backup
Other options according to Model code
The VLT® AutomationDrive represents a single drive concept that controlsthe entire range of operations from ordinary to servo like applicationson any machine or production line.
| Gross weight | 295.3 Kilogram | ||
| Net weight | 295 Kilogram | ||
| EAN | 5715253480046 |
| Product View (Switch) | GLBL | Global (Standard) | |
| Product Group | FC- | VLT® AutomationDrive FC- | |
| Series | 302 | 302 | |
| Power Rating | N710 | (N710) 710 KW / 1000 HP | |
| Phase | T | Three phase | |
| Mains Voltage | 7 | 525 - 690 VAC * | |
| Possible rating issue | WARN01 | Possible Rating Issue: | |
| Enclosure | E20 | (E20) IP20 / Chassis | |
| RFI Filter | H2 | RFI Filter | |
| Brake - Safe Stop | X | No brake chopper | |
| LCP | G | Graphical Loc. Cont. Panel | |
| Coating PCB | C | Coated PCB | |
| Mains Option | X | No Mains Option | |
| Adaptation A | X | Standard Cable Entries | |
| Adaptation B | X | No adaptation | |
| Software Release | SXXX | Latest release std. SW. | |
| Software Language Pack | X | Standard Language Pack | |
| A Option | AX | No A Option | |
| B Option | BK | MCB-101 General purp. I/O | |
| C0 Option MCO | CX | No C0 option | |
| C1 Option | X | No C1 option | |
| C Option Software | XX | No software option | |
| D Option | D0 | MCB-107 24V DC backup | |
| Frame Size | E4H | E4H | |
| Typecode Part 2 | XXXSXXXXAXBKCXXXXD0 | ||
| Product Catalog | NO_VIEW | NO VIEW | |
| Power 150% (HO) [KW] | 710 | 710 | |
| Power 110% (NO) [KW] | 800 | 800 | |
| Height [mm] | 1578,0 | 1578,0 | |
| Width w/ no C options [mm] | 607,0 | 607,0 | |
| Depth [mm] | 482,0 | 482,0 | |
| Depth with Option A/B [mm] | 482,0 | 482,0 | |
| kVA | 872 | 872 | |
| Power Loss NO [W] | 12723 | 12723 | |
| Power Loss NO [W] | 12321 | 12321 | |
| Power Loss HO [W] | 10319 | 10319 | |
| Power Loss HO [W] | 10060 | 10060 | |
| Continuous Current (NO) [A] | 889 | 889 | |
| Intermittent Current (NO) [A] | 978 | 978 | |
| Continuous Current (NO) [A] | 850 | 850 | |
| Intermittent Current (NO) [A] | 935 | 935 | |
| Continuous Current (HO) [A] | 763 | 763 | |
| Intermittent Current (HO) [A] | 1144 | 1144 | |
| Continuous Current (HO) [A] | 730 | 730 | |
| Intermittent Current (HO) [A] | 1095 | 1095 | |
| Power Rating at 525-550V | 560kW | 560kW | |
| Power Rating at 575V | 750HP | 750HP | |
| Power Rating at 690V | 710kW | 710kW | |
| Calculated Gross Weight [kg] | 295.3 | ||
| Calculated Net Weight [kg] | 295 | ||
| ECCN EU | Y901 | Y901 | |
| ECCN US | 3A999.a | 3A999.a | |
| Vendor | ERR01 | Cannot Determine Vendor | |
| Recommended Factory | ERR01 | Cannot Determine Vendor | |
| Modelcode01 | FC-302N710T7E20H2XGC | ||
| Modelcode02 | XXXSXXXXAXBKCXXXXD0 | ||
| Recommended Plant | ERR01 | ERR01 |