Frequency converter
FC-302N75KT7E2SH2XGCXXXSXXXXA0BXCXXXXD0
VLT® AutomationDrive FC-302
(N75K) 75 KW / 100 HP, Specific Ratings: 55kW@525-550V, 75HP@575V, 75kW@690V
Three phase, 525 - 690 VAC *,IP20 / Chassis - D3h Fra
RFI Filter
No brake chopper
Graphical Loc. Cont. Panel
Coated PCB, No Mains Option
Latest release std. SW.
Frame: D3H
PROFIBUS DP MCA 101, No B Option
No C1 option, MCB-107 24V DC backup
Other options according to Model code
The VLT® AutomationDrive represents a single drive concept that controlsthe entire range of operations from ordinary to servo like applicationson any machine or production line.
| Gross weight | 76 Kilogram | ||
| Net weight | 71 Kilogram | ||
| Volume | 228.095 Liter | ||
| EAN | 5710107996384 |
| Product View (Switch) | GLBL | Global (Standard) | |
| Product Group | FC- | VLT® AutomationDrive FC- | |
| Series | 302 | 302 | |
| Power Rating | N75K | (N75K) 75 KW / 100 HP | |
| Phase | T | Three phase | |
| Mains Voltage | 7 | 525 - 690 VAC * | |
| Possible rating issue | WARN01 | Possible Rating Issue: | |
| Enclosure | E2S | IP20 / Chassis - D3h Fra | |
| RFI Filter | H2 | RFI Filter | |
| Brake - Safe Stop | X | No brake chopper | |
| LCP | G | Graphical Loc. Cont. Panel | |
| Coating PCB | C | Coated PCB | |
| Mains Option | X | No Mains Option | |
| Adaptation A | X | Standard Cable Entries | |
| Adaptation B | X | No adaptation | |
| Software Release | SXXX | Latest release std. SW. | |
| Software Language Pack | X | Standard Language Pack | |
| A Option | A0 | PROFIBUS DP MCA 101 | |
| B Option | BX | No B Option | |
| C0 Option MCO | CX | No C0 option | |
| C1 Option | X | No C1 option | |
| C Option Software | XX | No software option | |
| D Option | D0 | MCB-107 24V DC backup | |
| Frame Size | D3H | D3H | |
| Typecode Part 2 | XXXSXXXXA0BXCXXXXD0 | ||
| Product Catalog | NO_VIEW | NO VIEW | |
| Power 150% (HO) [KW] | 75 | 75 | |
| Power 110% (NO) [KW] | 90 | 90 | |
| Height [mm] | 909,0 | 909,0 | |
| Height w/ Regen/Loadshare [mm] | 1004,0 | 1004,0 | |
| Width w/ no C options [mm] | 250,0 | 250,0 | |
| Depth [mm] | 375,0 | 375,0 | |
| Depth with Option A/B [mm] | 375,0 | 375,0 | |
| kVA | 103 | 103 | |
| Power Loss NO [W] | 1428 | 1428 | |
| Power Loss NO [W] | 1477 | 1477 | |
| Power Loss HO [W] | 1162 | 1162 | |
| Power Loss HO [W] | 1205 | 1205 | |
| Continuous Current (NO) [A] | 113 | 113 | |
| Intermittent Current (NO) [A] | 124 | 124 | |
| Continuous Current (NO) [A] | 108 | 108 | |
| Intermittent Current (NO) [A] | 119 | 119 | |
| Continuous Current (HO) [A] | 90 | 90 | |
| Intermittent Current (HO) [A] | 135 | 135 | |
| Continuous Current (HO) [A] | 86 | 86 | |
| Intermittent Current (HO) [A] | 129 | 129 | |
| Power Rating at 525-550V | 55kW | 55kW | |
| Power Rating at 575V | 75HP | 75HP | |
| Power Rating at 690V | 75kW | 75kW | |
| Calculated Gross Weight [kg] | 62.3 | ||
| Calculated Net Weight [kg] | 62 | ||
| ECCN EU | Y901 | Y901 | |
| ECCN US | 3A999.a | 3A999.a | |
| Vendor | ERR01 | Cannot Determine Vendor | |
| Recommended Factory | ERR01 | Cannot Determine Vendor | |
| Modelcode01 | FC-302N75KT7E2SH2XGC | ||
| Modelcode02 | XXXSXXXXA0BXCXXXXD0 | ||
| Recommended Plant | ERR01 | ERR01 |