Frequency converter
FC-302P22KT2E20H5BGCXXXSXXXXAXBRCXRXXDX
VLT® AutomationDrive FC-302
(P22K) 22 KW / 30 HP,
Three phase, 200 - 240 VAC,(E20) IP20 / Chassis
Marine,ruggedis RFI A2(C3)
Brake chopper
Graphical Loc. Cont. Panel
Coated PCB, No Mains Option
Latest release std. SW.
Frame: C3
No A Option, MCB-102 Encoder Option
MCB-113 Ext. Relay Card, No D option
Other options according to Model code
The VLT® AutomationDrive represents a single drive concept that controlsthe entire range of operations from ordinary to servo like applicationson any machine or production line.
| Gross weight | 39.72 Kilogram | ||
| Net weight | 36.87 Kilogram | ||
| EAN | 5715253740874 |
| Product View (Switch) | GLBL | Global (Standard) | |
| Product Group | FC- | VLT® AutomationDrive FC- | |
| Series | 302 | 302 | |
| Power Rating | P22K | (P22K) 22 KW / 30 HP | |
| Phase | T | Three phase | |
| Mains Voltage | 2 | 200 - 240 VAC | |
| Enclosure | E20 | (E20) IP20 / Chassis | |
| RFI Filter | H5 | Marine,ruggedis RFI A2(C3) | |
| Brake - Safe Stop | B | Brake chopper | |
| LCP | G | Graphical Loc. Cont. Panel | |
| Coating PCB | C | Coated PCB | |
| Mains Option | X | No Mains Option | |
| Adaptation A | X | Standard Cable Entries | |
| Adaptation B | X | No adaptation | |
| Software Release | SXXX | Latest release std. SW. | |
| Software Language Pack | X | Standard Language Pack | |
| A Option | AX | No A Option | |
| B Option | BR | MCB-102 Encoder Option | |
| C0 Option MCO | CX | No C0 option | |
| C1 Option | R | MCB-113 Ext. Relay Card | |
| C Option Software | XX | No software option | |
| D Option | DX | No D option | |
| Frame Size | C3 | C3 | |
| Typecode Part 2 | XXXSXXXXAXBRCXRXXDX | ||
| Product Catalog | NO_VIEW | NO VIEW | |
| Power 150% (HO) [KW] | 22 | 22 | |
| Power 110% (NO) [KW] | 30 | 30 | |
| Height [mm] | 550,0 | 550,0 | |
| Width w/ no C options [mm] | 308,0 | 308,0 | |
| Depth [mm] | 333,0 | 333,0 | |
| Depth with Option A/B [mm] | 333,0 | 333,0 | |
| kVA | 31.7 | 31.7 | |
| Power Loss NO [W] | 1140 | 1140 | |
| Power Loss HO [W] | 874 | 874 | |
| Continuous Current (NO) [A] | 115 | 115 | |
| Intermittent Current (NO) [A] | 127 | 127 | |
| Calculated Gross Weight [kg] | 39.72 | ||
| Calculated Net Weight [kg] | 36.87 | ||
| ECCN EU | Y901 | Y901 | |
| ECCN US | 3A999.a | 3A999.a | |
| Plant from Orderline | D902 | D902 | |
| Vendor | ERR01 | Cannot Determine Vendor | |
| Recommended Factory | ERR01 | Cannot Determine Vendor | |
| Modelcode01 | FC-302P22KT2E20H5BGC | ||
| Modelcode02 | XXXSXXXXAXBRCXRXXDX |